MODEL : BCSA12-2420A
INPUT
I/P : 230V AC, 1-Ph, 40-60Hz
Range : 180-270V AC
Fuse Protection.
I/P MOV
Soft Start
Inrush current : 92A@230V AC
OUTPUT
Nominal Battery Voltage : 12V DC / 24V DC (selector switch provided to
select the 12V or 24V)
Float Voltage : 13.5V / 27V
Boost Voltage : 14.4V / 28.8V
Top up Voltage : 15.6V / 31.2V(only for Lead acid battery)
Manual –Voltage adj. : 12-16.5V / 24-33V
Current : 20A (adj. 5-20A)
Line Regulation : +/- 1%
Load Regulation : +/- 1%
Ripple : +/- 1% (P-P)
Protections : a) Overload Protection auto recovery type.
b) Short circuit protection auto recovery type.
c) OVP Protection Latching type.
d) Reverse Polarity by fuse & MCB.
Current Limit : Yes
ENVIRONMENTAL
Operating temperature upto 500 C.
Humidity : < 95% Rh
IP 21 Protection
GENERAL
Digital Voltmeter & Currentmeter provided
Input and output MCB provided
Auto / Manual switch provided
Jumper provided to select the battery type – SMF/ Lead Acid
Potential Free Contact – Alarm contact –?????
Isolation : Input to Output – 1.5KV
Input to Earth – 1.5KV
Output to Earth- 500V
MTBF : 50K Hrs to MIL
INDICATIONS LED : a) Float
b) Boost
c) Equiliser
g) Top up
MECHANICAL
Dimension : 260(W) X 155(D) X 220(H)mm
Cooling type : Fan
Weight : 5.5 Kgs
OPTIONAL
Load and Battery Terminal separate.
2 Years Warranty
Specification subject to change as per our continuous developments