Specifications

MODEL                                    : BCSA12-2420A

INPUT
I/P                                        : 230V AC, 1-Ph, 40-60Hz
Range                                    : 180-270V AC
Fuse Protection.
I/P MOV
Soft Start
Inrush current                      : 92A@230V AC

OUTPUT
Nominal Battery Voltage         : 12V DC / 24V DC (selector switch provided to 
select the 12V or 24V)
Float Voltage                         : 13.5V / 27V
Boost Voltage                        : 14.4V / 28.8V
Top up Voltage                       : 15.6V / 31.2V(only for Lead acid battery)
Manual –Voltage adj.               : 12-16.5V / 24-33V
Current                                  : 20A (adj. 5-20A)
Line Regulation                       : +/- 1%
Load Regulation                      : +/- 1%
Ripple                                    : +/- 1% (P-P)
Protections                            : a) Overload Protection auto recovery type.
b) Short circuit protection auto recovery type.
c) OVP Protection Latching type.
d) Reverse Polarity by fuse & MCB.
Current Limit : Yes

ENVIRONMENTAL 
Operating temperature upto 500 C.
Humidity                               : < 95% Rh
IP 21 Protection

GENERAL
Digital Voltmeter & Currentmeter provided
Input and output MCB provided
Auto / Manual switch provided
Jumper provided to select the battery type – SMF/ Lead Acid
Potential Free Contact – Alarm contact –?????
Isolation                              : Input to Output – 1.5KV
Input to Earth – 1.5KV
Output to Earth- 500V
MTBF                                  : 50K Hrs to MIL

INDICATIONS LED           : a) Float
b) Boost
c) Equiliser
g) Top up

MECHANICAL
Dimension                                 : 260(W) X 155(D) X 220(H)mm
Cooling type                             : Fan
Weight                                    : 5.5 Kgs

 

OPTIONAL

Load and Battery Terminal separate.      

2 Years Warranty